==Modbus Master (SCADA) component== | ==Modbus Master (SCADA) component== | ||
Modbus component for talking to Modbus compatible hardware via RS232 or RS485. | Modbus component for talking to Modbus compatible hardware via RS232 or RS485. | ||
+ | |||
+ | ==Component Source Code== | ||
+ | |||
+ | Please click here to download the component source project: [https://www.flowcode.co.uk/wiki/componentsource/FC_Comp_Source_Modbus_SCADA.fcsx FC_Comp_Source_Modbus_SCADA.fcsx] | ||
+ | |||
+ | Please click here to view the component source code (Beta): [https://www.flowcode.co.uk/FlowchartView/?wfile=componentsource/FC_Comp_Source_Modbus_SCADA.fcsx FC_Comp_Source_Modbus_SCADA.fcsx] | ||
==Detailed description== | ==Detailed description== | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
Line 24: | Line 48: | ||
==Examples== | ==Examples== | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
Line 33: | Line 75: | ||
− | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | ==Macro reference== | ||
+ | |||
+ | ===ChangeFrameType=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ChangeFrameType''' |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Default frame type is the type set in the component properties. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | Type |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 0 = Modbus RTU / 1 = Modbus ASCII |
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID |
− | | width="90%" | | + | | width="90%" style="border-top: 2px solid #000;" | ''Return'' |
+ | |} | ||
+ | |||
+ | |||
+ | ===GetResponse=== | ||
+ | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
− | | | + | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] |
+ | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponse''' | ||
|- | |- | ||
− | | | + | | colspan="2" | Collects as much incoming data as possible and stored into the response buffer. The number of bytes received will be stored into location 0 of the response buffer. Return value indicates validity of incoming CRC. 0 = OK, 1 = CRC fail, 255 = No Data |
− | |||
|- | |- | ||
− | |||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 63: | Line 120: | ||
+ | ===GetResponseByte=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseByte''' |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Reads a byte from the last received response. The Index parametes specifies which byte to read back. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | Index |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 0=NumBytes, 1=SlaveAddress, 2=FunctionCode/ExceptionCode, 3=DataBytes, 4=data0, 5=data1, .. |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 91: | Line 139: | ||
+ | ===GetResponseInt=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseInt''' |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Reads a 16-bit value from the last received response. The Index parametes specifies the byte index of the value to read back. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | Index |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 4=data0, 6=data1, 8=data2, .. |
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90%" | | + | | width="90%" style="border-top: 2px solid #000;" | ''Return'' |
+ | |} | ||
+ | |||
+ | |||
+ | ===Initialise=== | ||
+ | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
− | | | + | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] |
+ | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''Initialise''' | ||
|- | |- | ||
− | | | + | | colspan="2" | Starts up the UART to allow communications |
− | |||
|- | |- | ||
− | |||
|- | |- | ||
− | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9- | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID |
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} | ||
+ | ===ReadAnalogInput=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadAnalogInput''' |
+ | |- | ||
+ | | colspan="2" | This command requests the analogue input register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. | ||
+ | |- | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
+ | | width="90%" | SlaveID | ||
+ | |- | ||
+ | | colspan="2" | The ID of the MODBUS slave | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
+ | | width="90%" | RegAddress | ||
+ | |- | ||
+ | | colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ... | ||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
+ | | width="90%" | RegCount | ||
|- | |- | ||
+ | | colspan="2" | Number of consecutive inputs to read, starting from RegAddress | ||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 132: | Line 201: | ||
+ | ===ReadCoil=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadCoil''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command requests the ON/OFF status of discrete coils starting from the start CoilAddress and going through to CoilAddress plus CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 154: | Line 224: | ||
|- | |- | ||
| colspan="2" | Number of consecutive coils to try and read | | colspan="2" | Number of consecutive coils to try and read | ||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 165: | Line 230: | ||
+ | ===ReadDigitalInput=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadDigitalInput''' |
+ | |- | ||
+ | | colspan="2" | This command requests the ON/OFF status of discrete inputs starting from the start DataAddress and going through to DataAddress plus DataCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. | ||
+ | |- | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
+ | | width="90%" | SlaveID | ||
+ | |- | ||
+ | | colspan="2" | The ID of the MODBUS slave | ||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
+ | | width="90%" | DataAddress | ||
|- | |- | ||
+ | | colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ... | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90%" | | + | | width="90%" | DataCount |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Number of consecutive inputs to read, starting from RegAddress |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 183: | Line 259: | ||
+ | ===ReadHoldingRegister=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadHoldingRegister''' |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | This command requests the analogue holding register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90%" | | + | | width="90%" | SlaveID |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | The ID of the MODBUS slave |
|- | |- | ||
− | | width="10%" align="center | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90% | + | | width="90%" | RegAddress |
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | colspan="2" | Address: 0=40001, 1=40002, ... |
− | |||
|- | |- | ||
− | | | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
+ | | width="90%" | RegCount | ||
|- | |- | ||
+ | | colspan="2" | Number of consecutive registers to read, starting from RegAddress | ||
|- | |- | ||
− | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | |
− | |||
− | |||
− | |||
− | |||
− | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9- | ||
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} | ||
+ | ===SetCoil=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoil''' |
|- | |- | ||
− | | colspan="2" | This command writes the contents of | + | | colspan="2" | This command writes the contents of a discrete coil at the location CoilAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 233: | Line 303: | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | CoilAddress |
|- | |- | ||
− | | colspan="2" | Address: 0= | + | | colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... |
|- | |- | ||
− | | width="10%" align="center" | [[File:Fc9- | + | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE |
− | | width="90%" | | + | | width="90%" | CoilState |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | 0=Off, 1=On |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 252: | Line 317: | ||
+ | ===SetCoils=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoils''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command writes the contents of a series of discrete coils at the location starting at CoilAddress through to CoilAddress + CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 266: | Line 332: | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | CoilAddress |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | CoilCount |
+ | |- | ||
+ | | colspan="2" | Number of consecutive coils to try and read | ||
+ | |- | ||
+ | | width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE | ||
+ | | width="90%" | CoilData | ||
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | An array of bytes each containing 8 1-bit coil values |
|- | |- | ||
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | ||
Line 280: | Line 351: | ||
+ | ===SetHoldingRegister=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
Line 308: | Line 380: | ||
+ | ===SetHoldingRegisters=== | ||
{| class="wikitable" style="width:60%; background-color:#FFFFFF;" | {| class="wikitable" style="width:60%; background-color:#FFFFFF;" | ||
|- | |- | ||
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]] | ||
− | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | ''' | + | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetHoldingRegisters''' |
|- | |- | ||
− | | colspan="2" | This command | + | | colspan="2" | This command writes the contents of several holding registers starting at the location RegAddress through to location RegAddress + RegCount . Returns 0 for success, 1 for CRC fail and 255 for no reply. |
|- | |- | ||
|- | |- | ||
Line 322: | Line 395: | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | RegAddress |
|- | |- | ||
− | | colspan="2" | | + | | colspan="2" | Address: 0=40001, 1=40002, ... |
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT | ||
− | | width="90%" | | + | | width="90%" | RegCount |
|- | |- | ||
− | | colspan="2" | Number of consecutive | + | | colspan="2" | Number of consecutive registers to write, starting from RegAddress |
|- | |- | ||
− | | width="10%" align="center | + | | width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT |
− | | width="90% | + | | width="90%" | RegValue |
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | colspan="2" | Array of values to send to the registers |
− | |||
|- | |- | ||
− | + | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE | |
− | |||
− | |||
− | | width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9- | ||
| width="90%" style="border-top: 2px solid #000;" | ''Return'' | | width="90%" style="border-top: 2px solid #000;" | ''Return'' | ||
|} | |} | ||
− | |||
− | |||
Line 357: | Line 420: | ||
| width="10%" align="center" style="background-color:#D8C9D8;" | [[File:Fc9-prop-icon.png]] | | width="10%" align="center" style="background-color:#D8C9D8;" | [[File:Fc9-prop-icon.png]] | ||
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''Properties''' | | width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''Properties''' | ||
+ | |- | ||
+ | |- | ||
+ | | width="10%" align="center" style="background-color:#EAE1EA;" | [[File:Fc9-conn-icon.png]] | ||
+ | | width="90%" style="background-color:#EAE1EA; color:#4B008D;" | Modbus Properties | ||
|- | |- | ||
|- | |- | ||
Line 388: | Line 455: | ||
|- | |- | ||
| colspan="2" | Number of timeouts in a row to wait for until we decide the slave is not responding or finished responding to a message. Range: 0 - 255 0 = First Timeout Only 1 = First Timeout + 1 2 = First Timeout + 2 | | colspan="2" | Number of timeouts in a row to wait for until we decide the slave is not responding or finished responding to a message. Range: 0 - 255 0 = First Timeout Only 1 = First Timeout + 1 2 = First Timeout + 2 | ||
+ | |- | ||
+ | | width="10%" align="center" style="background-color:#EAE1EA;" | [[File:Fc9-conn-icon.png]] | ||
+ | | width="90%" style="background-color:#EAE1EA; color:#4B008D;" | Runtime Properties | ||
+ | |- | ||
|- | |- | ||
| width="10%" align="center" | [[File:Fc9-type-10-icon.png]] | | width="10%" align="center" | [[File:Fc9-type-10-icon.png]] | ||
Line 423: | Line 494: | ||
|- | |- | ||
| colspan="2" | COM port data rate in bits per second | | colspan="2" | COM port data rate in bits per second | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|} | |} |
Latest revision as of 13:12, 7 February 2023
Author | Matrix TSL |
Version | 2.1 |
Category | Comms: System |
Contents
Modbus Master (SCADA) component
Modbus component for talking to Modbus compatible hardware via RS232 or RS485.
Component Source Code
Please click here to download the component source project: FC_Comp_Source_Modbus_SCADA.fcsx
Please click here to view the component source code (Beta): FC_Comp_Source_Modbus_SCADA.fcsx
Detailed description
No detailed description exists yet for this component
Examples
No additional examples
Macro reference
ChangeFrameType
![]() |
ChangeFrameType |
Default frame type is the type set in the component properties. | |
![]() |
Type |
0 = Modbus RTU / 1 = Modbus ASCII | |
![]() |
Return |
GetResponse
GetResponseByte
GetResponseInt
![]() |
GetResponseInt |
Reads a 16-bit value from the last received response. The Index parametes specifies the byte index of the value to read back. | |
![]() |
Index |
4=data0, 6=data1, 8=data2, .. | |
![]() |
Return |
Initialise
![]() |
Initialise |
Starts up the UART to allow communications | |
![]() |
Return |
ReadAnalogInput
ReadCoil
ReadDigitalInput
ReadHoldingRegister
SetCoil
SetCoils
SetHoldingRegister
SetHoldingRegisters