Component: Modbus Master (SCADA) (Comms: System): Difference between revisions

From Flowcode Help
XML import
 
No edit summary
 
(15 intermediate revisions by the same user not shown)
Line 1: Line 1:
 
{| style="width:50%"
 
{| width="50%"
|-
|-
| width="20%" style="color: gray;" | Author
| width="20%" style="color:gray;" | Author
| Matrix TSL
| Matrix TSL
|-
|-
| width="20%" style="color: gray;" | Version
| width="20%" style="color:gray;" | Version
| 2.1 (Release)
| 2.1
|-
|-
| width="20%" style="color: gray;" | Category
| width="20%" style="color:gray;" | Category
| Comms: System
| Comms: System
|}
|}




 
==Modbus Master (SCADA) component==
==[[File:Component Icon 97647329_1e06_46dc_ba11_9d721038294d.png|Image]] Modbus Master (SCADA) component==
Modbus component for talking to Modbus compatible hardware via RS232 or RS485.  
Modbus component for talking to Modbus compatible hardware via RS232 or RS485.  


==Examples==
==Component Source Code==
''<span style="color:red;">No additional examples</span>''


Please click here to download the component source project: [https://www.flowcode.co.uk/wiki/componentsource/FC_Comp_Source_Modbus_SCADA.fcsx FC_Comp_Source_Modbus_SCADA.fcsx]


==Downloadable macro reference==
Please click here to view the component source code (Beta): [https://www.flowcode.co.uk/FlowchartView/?wfile=componentsource/FC_Comp_Source_Modbus_SCADA.fcsx FC_Comp_Source_Modbus_SCADA.fcsx]


===<span style="font-weight: normal;"><u><tt>ReadHoldingRegister</tt></u></span>===
==Detailed description==
This command requests the analogue holding register values starting from the start RegAddress and going through to RegAddress plus RegCount.


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''


:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''RegAddress''
::Address: 0=40001, 1=40002, ...


:[[Variable Types|UINT]] ''RegCount''
::Number of consecutive registers to read, starting from RegAddress




'''Return value'''


:[[Variable Types|BYTE]]




===<span style="font-weight: normal;"><u><tt>ForceMultipleCoils</tt></u></span>===
This command writes the contents of a series of discrete coils at the location starting at CoilAddress through to CoilAddress + CoilCount.


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''


:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''CoilAddress''
::Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...


:[[Variable Types|UINT]] ''CoilCount''
::Number of consecutive coils to try and read


:[[Variable Types|BYTE]] ''CoilData''
::An array of bytes each containing 8 1-bit coil values




'''Return value'''


:[[Variable Types|BYTE]]




===<span style="font-weight: normal;"><u><tt>ForceSingleCoil</tt></u></span>===
This command writes the contents of a discrete coil at the location CoilAddress.


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''
''No detailed description exists yet for this component''


:[[Variable Types|UINT]] ''SlaveID''
==Examples==
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''CoilAddress''
::Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...


:[[Variable Types|BYTE]] ''CoilState''
::0=Off, 1=On




'''Return value'''


:[[Variable Types|BYTE]]




===<span style="font-weight: normal;"><u><tt>GetResponse</tt></u></span>===
Collects as much incoming data as possible and stored into the response buffer. The number of bytes received will be stored into location 0 of the response buffer.


Return value indicates validity of incoming CRC. 0 = OK, 1 = CRC fail, 255 = No Data


'''Parameters'''


:''This macro has no parameters''




'''Return value'''


:[[Variable Types|BYTE]]




===<span style="font-weight: normal;"><u><tt>ReadCoilStatus</tt></u></span>===
This command requests the ON/OFF status of discrete coils starting from the start CoilAddress and going through to CoilAddress plus CoilCount.


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''


:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''CoilAddress''
::Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...


:[[Variable Types|UINT]] ''CoilCount''
::Number of consecutive coils to try and read




'''Return value'''


:[[Variable Types|BYTE]]


''<span style="color:red;">No additional examples</span>''


===<span style="font-weight: normal;"><u><tt>GetResponseByte</tt></u></span>===
Reads a byte from the last received response. The Index parametes specifies which byte to read back.


'''Parameters'''


:[[Variable Types|BYTE]] ''Index''
::0=NumBytes, 1=SlaveAddress, 2=FunctionCode/ExceptionCode, .....




'''Return value'''


:[[Variable Types|BYTE]]




===<span style="font-weight: normal;"><u><tt>ReadInputStatus</tt></u></span>===
This command requests the ON/OFF status of discrete inputs starting from the start DataAddress and going through to DataAddress plus DataCount.


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''


:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''DataAddress''
==Macro reference==
::Input Address: 0=10001, 1=10002, 2=10003, ...


:[[Variable Types|UINT]] ''DataCount''
===ChangeFrameType===
::Number of consecutive inputs to read, starting from RegAddress
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ChangeFrameType'''
|-
| colspan="2" | Default frame type is the type set in the component properties.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" | Type
|-
| colspan="2" | 0 = Modbus RTU / 1 = Modbus ASCII&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}




'''Return value'''
===GetResponse===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponse'''
|-
| colspan="2" | Collects as much incoming data as possible and stored into the response buffer. The number of bytes received will be stored into location 0 of the response buffer. Return value indicates validity of incoming CRC. 0 = OK, 1 = CRC fail, 255 = No Data&nbsp;
|-
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


:[[Variable Types|BYTE]]


===GetResponseByte===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseByte'''
|-
| colspan="2" | Reads a byte from the last received response. The Index parametes specifies which byte to read back. &nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" | Index
|-
| colspan="2" | 0=NumBytes, 1=SlaveAddress, 2=FunctionCode/ExceptionCode, 3=DataBytes, 4=data0, 5=data1, ..&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


===<span style="font-weight: normal;"><u><tt>ChangeFrameType</tt></u></span>===
Default frame type is the type set in the component properties.


'''Parameters'''
===GetResponseInt===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''GetResponseInt'''
|-
| colspan="2" | Reads a 16-bit value from the last received response.  The Index parametes specifies the byte index of the value to read back. &nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" | Index
|-
| colspan="2" | 4=data0, 6=data1, 8=data2, ..&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


:[[Variable Types|BYTE]] ''Type''
::0 = Modbus RTU / 1 = Modbus ASCII


===Initialise===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''Initialise'''
|-
| colspan="2" | Starts up the UART to allow communications&nbsp;
|-
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-void-icon.png]] - VOID
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


'''Return value'''


:''This call does not return a value''
===ReadAnalogInput===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadAnalogInput'''
|-
| colspan="2" | This command requests the analogue input register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegAddress
|-
| colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegCount
|-
| colspan="2" | Number of consecutive inputs to read, starting from RegAddress&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}




===<span style="font-weight: normal;"><u><tt>PresetSingleRegister</tt></u></span>===
===ReadCoil===
This command writes the contents of a analogue output holding registerl at the location RegAddress.
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadCoil'''
|-
| colspan="2" | This command requests the ON/OFF status of discrete coils starting from the start CoilAddress and going through to CoilAddress plus CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | CoilAddress
|-
| colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | CoilCount
|-
| colspan="2" | Number of consecutive coils to try and read&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


Returns 0 for success, 1 for CRC fail and 255 for no reply.


'''Parameters'''
===ReadDigitalInput===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadDigitalInput'''
|-
| colspan="2" | This command requests the ON/OFF status of discrete inputs starting from the start DataAddress and going through to DataAddress plus DataCount. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | DataAddress
|-
| colspan="2" | Input Address: 0=10001, 1=10002, 2=10003, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | DataCount
|-
| colspan="2" | Number of consecutive inputs to read, starting from RegAddress&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave


:[[Variable Types|UINT]] ''RegAddress''
===ReadHoldingRegister===
::Address: 0=40001, 1=40002, ...
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''ReadHoldingRegister'''
|-
| colspan="2" | This command requests the analogue holding register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegAddress
|-
| colspan="2" | Address: 0=40001, 1=40002, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegCount
|-
| colspan="2" | Number of consecutive registers to read, starting from RegAddress&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


:[[Variable Types|UINT]] ''RegValue''
::Value to send to the selected register


===SetCoil===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoil'''
|-
| colspan="2" | This command writes the contents of a discrete coil at the location CoilAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | CoilAddress
|-
| colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" | CoilState
|-
| colspan="2" | 0=Off, 1=On&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


'''Return value'''


:[[Variable Types|BYTE]]
===SetCoils===
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetCoils'''
|-
| colspan="2" | This command writes the contents of a series of discrete coils at the location starting at CoilAddress through to CoilAddress + CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | CoilAddress
|-
| colspan="2" | Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | CoilCount
|-
| colspan="2" | Number of consecutive coils to try and read&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" | CoilData
|-
| colspan="2" | An array of bytes each containing 8 1-bit coil values&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}




===<span style="font-weight: normal;"><u><tt>GetResponseInt</tt></u></span>===
===SetHoldingRegister===
Reads a 16-bit value from the last received response.  
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
|-
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetHoldingRegister'''
|-
| colspan="2" | This command writes the contents of a holding register at the location RegAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
|-
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | SlaveID
|-
| colspan="2" | The ID of the MODBUS slave&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegAddress
|-
| colspan="2" | Address: 0=40001, 1=40002, ...&nbsp;
|-
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
| width="90%" | RegValue
|-
| colspan="2" | Value to send to the selected register&nbsp;
|-
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
| width="90%" style="border-top: 2px solid #000;" | ''Return''
|}


The Index parametes specifies the byte index of the value to read back.


'''Parameters'''
===SetHoldingRegisters===
 
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
:[[Variable Types|BYTE]] ''Index''
|-
::0=NumBytes, 1=SlaveAddress, 2=FunctionCode/ExceptionCode, .....
| width="10%" align="center" style="background-color:#D8C9D8;" align="center" | [[File:Fc9-comp-macro.png]]
 
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''SetHoldingRegisters'''
 
|-
'''Return value'''
| colspan="2" | This command writes the contents of several holding registers starting at the location RegAddress through to location RegAddress + RegCount . Returns 0 for success, 1 for CRC fail and 255 for no reply.&nbsp;
 
|-
:[[Variable Types|UINT]]
|-
 
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
 
| width="90%" | SlaveID
===<span style="font-weight: normal;"><u><tt>ReadInputRegister</tt></u></span>===
|-
This command requests the analogue input register values starting from the start RegAddress and going through to RegAddress plus RegCount.
| colspan="2" | The ID of the MODBUS slave&nbsp;
 
|-
Returns 0 for success, 1 for CRC fail and 255 for no reply.
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
 
| width="90%" | RegAddress
'''Parameters'''
|-
 
| colspan="2" | Address: 0=40001, 1=40002, ...&nbsp;
:[[Variable Types|UINT]] ''SlaveID''
|-
::The ID of the MODBUS slave
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
 
| width="90%" | RegCount
:[[Variable Types|UINT]] ''RegAddress''
|-
::Input Address: 0=10001, 1=10002, 2=10003, ...
| colspan="2" | Number of consecutive registers to write, starting from RegAddress&nbsp;
 
|-
:[[Variable Types|UINT]] ''RegCount''
| width="10%" align="center" | [[File:Fc9-u16-icon.png]] - UINT
::Number of consecutive inputs to read, starting from RegAddress
| width="90%" | RegValue
 
|-
 
| colspan="2" | Array of values to send to the registers&nbsp;
'''Return value'''
|-
 
| width="10%" align="center" style="border-top: 2px solid #000;" | [[File:Fc9-u8-icon.png]] - BYTE
:[[Variable Types|BYTE]]
| width="90%" style="border-top: 2px solid #000;" | ''Return''
 
|}
 
===<span style="font-weight: normal;"><u><tt>PresetMultipleRegisters</tt></u></span>===
This command writes the contents of several analogue output holding registers starting at the location RegAddress through to location RegAddress + RegCount .
 
Returns 0 for success, 1 for CRC fail and 255 for no reply.
 
'''Parameters'''
 
:[[Variable Types|UINT]] ''SlaveID''
::The ID of the MODBUS slave
 
:[[Variable Types|UINT]] ''RegAddress''
::Address: 0=40001, 1=40002, ...
 
:[[Variable Types|UINT]] ''RegCount''
::Number of consecutive registers to write, starting from RegAddress
 
:[[Variable Types|UINT]] ''RegValue''
::Array of values to send to the registers
 
 
'''Return value'''
 
:[[Variable Types|BYTE]]
 
 
===<span style="font-weight: normal;"><u><tt>Initialise</tt></u></span>===
Starts up the UART to allow communications
 
'''Parameters'''
 
:''This macro has no parameters''
 
 
'''Return value'''
 
:''This call does not return a value''
 
 
 
==Simulation macro reference==
 
''This component does not contain any simulation macros''




==Property reference==
==Property reference==
<span style="font-weight: normal;"><u>Frame Type</u></span>


This property is of type ''Fixed list of ints'' and can be referenced with the variable name ''FrameType''.
{| class="wikitable" style="width:60%; background-color:#FFFFFF;"
 
|-
Switches between RTU and ASCII forms of Modbus
| width="10%" align="center" style="background-color:#D8C9D8;" | [[File:Fc9-prop-icon.png]]
 
| width="90%" style="background-color:#D8C9D8; color:#4B008D;" | '''Properties'''  
<span style="font-weight: normal;"><u>Receive Buffer Size</u></span>
|-
 
|-
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''ReceiveBufferSize''.
| width="10%" align="center" style="background-color:#EAE1EA;" | [[File:Fc9-conn-icon.png]]
 
| width="90%" style="background-color:#EAE1EA; color:#4B008D;" | Modbus Properties
Maximum number of bytes the receive buffer can hold
|-
 
|-
<span style="font-weight: normal;"><u>Slave ID Bytes</u></span>
| width="10%" align="center" | [[File:Fc9-type-16-icon.png]]
 
| width="90%" | Frame Type
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''AddressBytes''.
|-
 
| colspan="2" | Switches between RTU and ASCII forms of Modbus&nbsp;
Number of bytes used when passing a slave ID, usually 1 but sometimes 2
|-
 
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
<span style="font-weight: normal;"><u>Silent Interval</u></span>
| width="90%" | Receive Buffer Size
 
|-
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''SilentInterval''.
| colspan="2" | Maximum number of bytes the receive buffer can hold&nbsp;
 
|-
Configures how much time to wait after each master modbus command before another command can be sent.
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
 
| width="90%" | Slave ID Bytes
A silent interval of 60ms minimum is required in order to guarentee successful reception of the next transmission.
|-
 
| colspan="2" | Number of bytes used when passing a slave ID, usually 1 but sometimes 2&nbsp;
0=No Delay  
|-
 
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
60 = 60mS - Default
| width="90%" | Silent Interval
 
|-
Range : 0 - 65535
| colspan="2" | Configures how much time to wait after each master modbus command before another command can be sent. A silent interval of 60ms minimum is required in order to guarentee successful reception of the next transmission. 0=No Delay 60 = 60mS - Default Range : 0 - 65535&nbsp;
 
|-
<span style="font-weight: normal;"><u>UART Receive Timeout</u></span>
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
 
| width="90%" | UART Receive Timeout
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''RXTOUT''.
|-
 
| colspan="2" | Amount of time to wait before timing out when listening for a slave's response. Range: 0 - 255. 0 = Don't Wait 1 - 254 = X ms 255 = Wait Forever&nbsp;
Amount of time to wait before timing out when listening for a slave's response.
|-
 
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
Range: 0 - 255.
| width="90%" | Receive Timeout Count
 
|-
0 = Don't Wait
| colspan="2" | Number of timeouts in a row to wait for until we decide the slave is not responding or finished responding to a message. Range: 0 - 255 0 = First Timeout Only 1 = First Timeout + 1 2 = First Timeout + 2&nbsp;
 
|-
1 - 254 = X ms
| width="10%" align="center" style="background-color:#EAE1EA;" | [[File:Fc9-conn-icon.png]]
 
| width="90%" style="background-color:#EAE1EA; color:#4B008D;" | Runtime Properties
255 = Wait Forever
|-
 
|-
<span style="font-weight: normal;"><u>Receive Timeout Count</u></span>
| width="10%" align="center" | [[File:Fc9-type-10-icon.png]]
 
| width="90%" | Label
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''TOUTCNT''.
|-
 
| colspan="2" | A text label to appear on the Modbus panel object.&nbsp;
Number of timeouts in a row to wait for until we decide the slave is not responding or finished responding
|-
 
| width="10%" align="center" | [[File:Fc9-type-7-icon.png]]
to a message.
| width="90%" | Console Data
 
|-
Range: 0 - 255
| colspan="2" | Selects if the console data is automatically generated or not&nbsp;
 
|-
0 = First Timeout Only
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
 
| width="90%" | Console Columns
1 = First Timeout + 1
|-
 
| colspan="2" | Number of characters that can be displayed on a single line of the console.&nbsp;
2 = First Timeout + 2
|-
 
| width="10%" align="center" | [[File:Fc9-type-16-icon.png]]
<span style="font-weight: normal;"><u>Label</u></span>
| width="90%" | Data Source
 
|-
This property is of type ''Line of text'' and can be referenced with the variable name ''label''.
| colspan="2" | Simulation data source used to allow the component to connect to various remote devices    Nothing - Simulation data is ignored    COM port - Routes the communication data to and from a physical or virtual COM port     Injector - Routes the communication data via a data injector component on the Panel.&nbsp;
 
|-
A text label to appear on the Modbus panel object.
| width="10%" align="center" | [[File:Fc9-type-16-icon.png]]
 
| width="90%" | COM Port
<span style="font-weight: normal;"><u>Console Data</u></span>
|-
 
| colspan="2" | Lists all the current available COM port hardware on your PC.&nbsp;
This property is of type ''True or false'' and can be referenced with the variable name ''scada_uart1::ConsoleData''.
|-
 
| width="10%" align="center" | [[File:Fc9-type-7-icon.png]]
Selects if the console data is automatically generated or not
| width="90%" | Refresh Ports
 
|-
<span style="font-weight: normal;"><u>Console Columns</u></span>
| colspan="2" | &nbsp;
 
|-
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''scada_uart1::ConsoleColumns''.
| width="10%" align="center" | [[File:Fc9-type-21-icon.png]]
 
| width="90%" | Baud Rate
Number of characters that can be displayed on a single line of the console.
|-
 
| colspan="2" | COM port data rate in bits per second&nbsp;
<span style="font-weight: normal;"><u>Data Source</u></span>
|}
 
This property is of type ''Fixed list of ints'' and can be referenced with the variable name ''scada_uart1::DataSource''.
 
Simulation data source used to allow the component to connect to various remote devices
 
     Nothing - Simulation data is ignored
 
     COM port - Routes the communication data to and from a physical or virtual COM port  
 
    Injector - Routes the communication data via a data injector component on the Panel.
 
<span style="font-weight: normal;"><u>COM Port</u></span>
 
This property is of type ''Fixed list of ints'' and can be referenced with the variable name ''scada_uart1::com_port''.
 
Lists all the current available COM port hardware on your PC.
 
<span style="font-weight: normal;"><u>Baud Rate</u></span>
 
This property is of type ''Unsigned integer'' and can be referenced with the variable name ''scada_uart1::baud''.
 
COM port data rate in bits per second

Latest revision as of 13:12, 7 February 2023

Author Matrix TSL
Version 2.1
Category Comms: System


Modbus Master (SCADA) component

Modbus component for talking to Modbus compatible hardware via RS232 or RS485.

Component Source Code

Please click here to download the component source project: FC_Comp_Source_Modbus_SCADA.fcsx

Please click here to view the component source code (Beta): FC_Comp_Source_Modbus_SCADA.fcsx

Detailed description

No detailed description exists yet for this component

Examples

No additional examples







Macro reference

ChangeFrameType

ChangeFrameType
Default frame type is the type set in the component properties. 
- BYTE Type
0 = Modbus RTU / 1 = Modbus ASCII 
- VOID Return


GetResponse

GetResponse
Collects as much incoming data as possible and stored into the response buffer. The number of bytes received will be stored into location 0 of the response buffer. Return value indicates validity of incoming CRC. 0 = OK, 1 = CRC fail, 255 = No Data 
- BYTE Return


GetResponseByte

GetResponseByte
Reads a byte from the last received response. The Index parametes specifies which byte to read back.  
- BYTE Index
0=NumBytes, 1=SlaveAddress, 2=FunctionCode/ExceptionCode, 3=DataBytes, 4=data0, 5=data1, .. 
- BYTE Return


GetResponseInt

GetResponseInt
Reads a 16-bit value from the last received response. The Index parametes specifies the byte index of the value to read back.  
- BYTE Index
4=data0, 6=data1, 8=data2, .. 
- UINT Return


Initialise

Initialise
Starts up the UART to allow communications 
- VOID Return


ReadAnalogInput

ReadAnalogInput
This command requests the analogue input register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT RegAddress
Input Address: 0=10001, 1=10002, 2=10003, ... 
- UINT RegCount
Number of consecutive inputs to read, starting from RegAddress 
- BYTE Return


ReadCoil

ReadCoil
This command requests the ON/OFF status of discrete coils starting from the start CoilAddress and going through to CoilAddress plus CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT CoilAddress
Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... 
- UINT CoilCount
Number of consecutive coils to try and read 
- BYTE Return


ReadDigitalInput

ReadDigitalInput
This command requests the ON/OFF status of discrete inputs starting from the start DataAddress and going through to DataAddress plus DataCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT DataAddress
Input Address: 0=10001, 1=10002, 2=10003, ... 
- UINT DataCount
Number of consecutive inputs to read, starting from RegAddress 
- BYTE Return


ReadHoldingRegister

ReadHoldingRegister
This command requests the analogue holding register values starting from the start RegAddress and going through to RegAddress plus RegCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT RegAddress
Address: 0=40001, 1=40002, ... 
- UINT RegCount
Number of consecutive registers to read, starting from RegAddress 
- BYTE Return


SetCoil

SetCoil
This command writes the contents of a discrete coil at the location CoilAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT CoilAddress
Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... 
- BYTE CoilState
0=Off, 1=On 
- BYTE Return


SetCoils

SetCoils
This command writes the contents of a series of discrete coils at the location starting at CoilAddress through to CoilAddress + CoilCount. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT CoilAddress
Coil Address: 0=Coil1, 1=Coil2, 2=Coil3, ... 
- UINT CoilCount
Number of consecutive coils to try and read 
- BYTE CoilData
An array of bytes each containing 8 1-bit coil values 
- BYTE Return


SetHoldingRegister

SetHoldingRegister
This command writes the contents of a holding register at the location RegAddress. Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT RegAddress
Address: 0=40001, 1=40002, ... 
- UINT RegValue
Value to send to the selected register 
- BYTE Return


SetHoldingRegisters

SetHoldingRegisters
This command writes the contents of several holding registers starting at the location RegAddress through to location RegAddress + RegCount . Returns 0 for success, 1 for CRC fail and 255 for no reply. 
- UINT SlaveID
The ID of the MODBUS slave 
- UINT RegAddress
Address: 0=40001, 1=40002, ... 
- UINT RegCount
Number of consecutive registers to write, starting from RegAddress 
- UINT RegValue
Array of values to send to the registers 
- BYTE Return


Property reference

Properties
Modbus Properties
Frame Type
Switches between RTU and ASCII forms of Modbus 
Receive Buffer Size
Maximum number of bytes the receive buffer can hold 
Slave ID Bytes
Number of bytes used when passing a slave ID, usually 1 but sometimes 2 
Silent Interval
Configures how much time to wait after each master modbus command before another command can be sent. A silent interval of 60ms minimum is required in order to guarentee successful reception of the next transmission. 0=No Delay 60 = 60mS - Default Range : 0 - 65535 
UART Receive Timeout
Amount of time to wait before timing out when listening for a slave's response. Range: 0 - 255. 0 = Don't Wait 1 - 254 = X ms 255 = Wait Forever 
Receive Timeout Count
Number of timeouts in a row to wait for until we decide the slave is not responding or finished responding to a message. Range: 0 - 255 0 = First Timeout Only 1 = First Timeout + 1 2 = First Timeout + 2 
Runtime Properties
Label
A text label to appear on the Modbus panel object. 
Console Data
Selects if the console data is automatically generated or not 
Console Columns
Number of characters that can be displayed on a single line of the console. 
Data Source
Simulation data source used to allow the component to connect to various remote devices Nothing - Simulation data is ignored COM port - Routes the communication data to and from a physical or virtual COM port Injector - Routes the communication data via a data injector component on the Panel. 
COM Port
Lists all the current available COM port hardware on your PC. 
Refresh Ports
 
Baud Rate
COM port data rate in bits per second